MECHANICAL Electrical Instrumentation & Control Chemical Engineering Service & Maintenance Damper Smoke Damper Product Description: HI AIR KOREA (HAK) Smoke Dampers for nuclear power plants can be installed in HVAC systems provided for various buildings of nuclear power plants. HAK Smoke Dampers are used to prevent the spread of smoke from the space of fire origin to other spaces in the same building. These dampers are available as safety-related (SR) and non-safety-related (NSR) items. Safety related dampers are fabricated with Q-class components and dedicated commercial-grade items, and verified for seismic qualification (SQ). They can also be verified for environmental qualification (EQ). Specification: • Design Base - DA of ASME AG-1 (KEPIC MH) - IEEE 323 - IEEE 382 (KEPIC END 3700) - UL 555S - AMCA 500-D • Closes automatically using an Electro-Thermal Link (ETL) • Power Supply to Electro-Thermal Link (ETL shall be 120VAC or 24VDC) - Standard Construction - Frame: Carbon Steel + Hot-Dip Galvanized - Blade (Seat): Carbon Steel + Hot-Dip Galvanized - Fusible Link: ETL (Electro-thermal link) - Blade Seal: Silicone Foam Gasket - Shaft: Carbon Steel + Electro Galvanized • Leakage Classification Class Ⅰ in accordance with UL 555S Supplier Information • Hi Air Korea Co., Ltd. Domestic Track Records Main Client KHNP Project Name Saeul NPP #3,4 / Shin-Hanul NPP #1,2 Delivery Year 2016-2021 / 2011-2018 028 MECHANICAL