Mechanical ELECTRICAL Instrumentation & Control Chemical Engineering Service & Maintenance Domestic Track Records Main Client KHNP KHNP KHNP Project Name Saeul NPP #3, 4 for High & Low radiation area Kori NPP #3 for High & Low radiation Wolsong NPP #3 for Low radiation area Delivery Year 2020 ~ 2025 2020 2023 LED Lighting Fixture Series for Nuclear Facility Zones - General Utility & Reactor Containment Product Description: • Graphite LED Flood Light for High-Radiation areas • Compatible with ceiling, wall, pendant, and chain mounts • Comprehensive Coverage • Enhanced Termination Structures • LED Downlight(6”) for Low Radiation area • Comprehensive Coverage • Enhanced Termination Structures • LED Air supply / Heat exchange Recessed Lighting fixture for Inverted “T or M” Ceiling • Comprehensive Coverage • Enhanced Termination Structures Specification: • Common Features - Radiation Resistance TID 1 x 104 Gy ~ TID 8 x 105 Gy - EMC Compliance (US NRC 1.180 Reg.) - Temperature Endurance: 50℉ to 120℉ (10℃ to 49℃) ~ 50℉ to 150℉ (10℃ to 65.6℃) - Seismic Category Ⅱ,Ⅲ Compliance Supplier Information • Solux Co., Ltd. Light 118 ELECTRICAL